Speed Gates and Fire Alarms: What Happens During an Emergency?

Essential Security Supplies

Speed gates must not obstruct an approved escape route during a fire or other emergency. The required response may involve automatic barrier opening, an approved manual release or a compliant alternative route. Which solution applies depends on the building design, New Zealand requirements and the exact gate model. A normal access-control unlock command does not, by itself, demonstrate emergency egress compliance.

What happens when the fire alarm activates?

A speed gate that forms part of an escape route must not obstruct the approved means of escape. The correct response is determined by the building's fire design, route classification, applicable New Zealand Building Code provisions and the manufacturer's verified capabilities. It may involve barriers opening and remaining open, a suitable manual release mechanism or a compliant alternative escape route. These approaches are not universally interchangeable. An ordinary access-control unlock command does not necessarily create a usable escape passage.

New Zealand building requirements

Genuine FERN360 FGES-SGSW600-1 stainless steel swing speed gate shown as equipment reference for emergency-egress design
FERN360 FGES-SGSW600-1 swing speed gate. Genuine catalogue product photograph; emergency-release suitability must be confirmed for the exact installation.

Clause C4 of the New Zealand Building Code addresses movement to a place of safety. The 2025 C/AS2 second edition, section 3.9.6, restricts automatic doors and access control systems across escape routes leading into or within exitways. For permitted open-path or final-exit arrangements, section 3.9.6.1 sets out power-failure or malfunction escape provisions, and 3.9.6.2 addresses immediately adjacent alternative swing doors. These are specific requirements of the cited acceptable solution, not approval for any particular gate model. Clause D1 addresses access routes and accessibility. Designers must identify whether the proposed gate is in an open path, exitway or final exit, determine the relevant compliance pathway and account for occupants using mobility aids. A product described as fail-safe is not automatically compliant with any particular installation. The final design should be assessed by the responsible fire and building design professionals. See the official MBIE guidance at C/AS2.

Define the fire alarm interface

A fire-alarm interface can be implemented through an approved output, safety circuit or other documented control arrangement. The security integrator should coordinate with the fire-system designer, fire alarm contractor, electrical contractor and gate manufacturer. First identify the exact emergency event intended to trigger the gate response. Next confirm the output and gate input are electrically and functionally compatible. Determine the behaviour of the barriers, direction control and any anti-tailgating function while the alarm condition persists. Normal access permissions must not defeat the approved emergency passage. Finally specify the reset sequence, including any manual inspection or authorised reset required before the gates return to normal service. Avoid assuming that a network or software command is sufficient as the sole safety mechanism.

What happens if power fails?

Genuine FERN360 FGES-SGSL550-1 stainless steel sliding speed gate for power failure interface assessment
FERN360 FGES-SGSL550-1 sliding speed gate. Its pictured appearance does not establish a compliant power-failure response.

Power failure and fire alarm activation are different events. Some gates may operate correctly on an alarm signal while normal power is present, yet respond differently if their supply is interrupted. Review a mains failure, gate controller fault, communication fault and simultaneous alarm and supply failure. Identify whether a motor, spring, mechanical release or backup energy supply provides the required passage and verify each mechanism against the specific model's documentation. A battery-backed controller does not necessarily guarantee an open route. Record the actual physical barrier position and whether occupants can pass without a credential. Check the recovery sequence after power returns so the barriers do not close unsafely.

Accessible and alternative escape routes

An adjacent escape door can be part of an approved design, particularly where a standard gate lane does not provide suitable clear width or accessible passage. However, installing a door beside a gate is not proof of compliance. Confirm that the door is part of the approved route, leads to a usable destination, has the required clear opening and does not rely on a credential when emergency egress is required. Review locking hardware, signage, lighting, accessibility and obstructions. Allow for visitors who may be unfamiliar with the entrance. The route should work for people using wheelchairs or other mobility aids and for those requiring assistance, as established by the design. Consider NZS 4121 alongside the relevant Building Code accessibility provisions when assessing the accessible route.

Normal anti-tailgating versus emergency mode

Genuine FERN360 FGES-FB550-2 stainless steel flap barrier used to illustrate pedestrian lane control
FERN360 FGES-FB550-2 flap barrier. Normal pedestrian control must not override the approved emergency escape strategy.

During normal operation, speed gates may detect unauthorised followers, control passage direction and stop movement when a sensor reports a problem. Those controls can be useful for security, but they must not override the approved evacuation arrangement. Specify separate operating states for ordinary access, access denied, emergency release, equipment fault and restoration. Make the safety priority explicit in the cause-and-effect documentation. For a discussion of ordinary pedestrian control, read Speed Gate Tailgating Detection: How Effective Is It?. That topic is distinct from the emergency release function.

Commissioning sequence for installers

Agree the test procedure with the responsible building and fire-system parties before exercising any emergency interfaces. Verify normal authorised and denied access first. Then confirm the gate's response to the approved fire-alarm input and inspect the usable escape route. Record clear passage, barrier position and whether the release is maintained for the intended condition. Test controlled loss of normal power and, where the design requires it, the relevant combined fault scenarios. Check the designated accessible route and alternative escape door. After the alarm clears, confirm the approved reset and safe return to normal operation. A simulated contact at the gate controller may help local diagnostics, but it is not a substitute for end-to-end testing of the approved fire system. Never disconnect safety wiring or generate an evacuation without the required coordination and approvals.

What commissioning records should contain

Retain the approved entrance layout, escape-route requirements, product make and model, firmware where material, current manufacturer's installation instructions, interface drawings, power supply details and the documented cause-and-effect matrix. For every witnessed test note the date, responsible parties, trigger condition, expected outcome, observed outcome and any corrective actions. Re-test a failed function after correction. The gate's configuration and the responsible party for ongoing checks should be clear to the building operator. In New Zealand, a speed gate on a means of escape may fall within specified system SS 3/2 (access-controlled doors) where its security controls could trap occupants if they fail. Confirm the system classification and ensure it is recorded on the building's compliance schedule where required. The owner must arrange the routine inspections stated in that schedule; depending on the nominated performance and inspection standard, these can include owner checks and six-monthly and annual IQP inspections. Where the access-controlled system interfaces with the emergency warning system, the approved compliance schedule may require annual end-to-end interface testing. Hand over the cause-and-effect matrix, commissioning records and ongoing inspection requirements to the owner and IQP. See MBIE's Compliance Schedule Handbook for SS 3/2 guidance. Changes to gate hardware, controllers, firmware, wiring or building layout should trigger review of affected safety functions.

Common mistakes to avoid

Check whether each gate is described as fail-safe or fail-secure and precisely what those terms mean for its barrier, lock and power-loss behaviour. Fail-safe may mean release of a locking mechanism rather than a fully open, unobstructed lane; fail-secure configurations require particular scrutiny against the approved escape strategy. Some models offer mechanical break-out or push-open barrier arrangements, but do not assume a break-out mechanism is present or suitable without model-specific instructions and witnessed testing. Do not assume that every speed gate opens automatically in a fire. Emergency behaviour varies by equipment and configuration. Do not rely on a software unlock button as proof of a complete evacuation arrangement. Do not test only while mains power is available. Do not overlook accessible egress or the actual clear passage width. Do not assume that resetting an alarm should immediately close the barriers. Finally, do not treat a passed factory feature test as proof that the installed gate complies with a specific building's approved means of escape. The site design, complete interface and physical route all matter.

Planning a compliant entrance solution

Start with the approved escape strategy rather than selecting a gate solely by appearance or throughput. Establish the pedestrian flow, route width, accessible access requirements and fire-system interface, then identify equipment that can meet the specified functions. Obtain exact manufacturer evidence and coordinate an agreed commissioning plan. Compare suitable equipment in our Speed Gates range, with emergency-release suitability verified against the specific building design. Contact Essential Security Supplies for trade entrance-control specification enquiries. The catalogue examples pictured in this guide are reference photographs, not verified in-stock purchasing recommendations. Final fire safety and building compliance approval remains with the responsible qualified parties. Review the related Speed Gate Lane Sizing for NZ Buildings guidance when planning the entrance layout.

Frequently asked questions

Do all speed gates automatically open during a fire alarm?

No. Emergency behaviour depends on the equipment, configuration and approved building design. Verify the specific installation.

Must a speed gate open when power fails?

The installed system must meet the applicable escape requirements. An unlocked mechanism alone may not produce the required usable passage.

Can speed gates be installed on a fire escape route?

Only where the proposed arrangement meets the applicable route classification and approved compliance pathway. Some locations or arrangements are restricted.

Is an emergency push button sufficient?

Not by itself. The design must also address usable egress, accessibility, power failure and the complete fire-system interface.

Who should approve the fire alarm interface?

The responsible building and fire designers and other relevant approval parties must coordinate the design, with contractors testing their documented functions.